IEEJ Journal of Industry Applications
Online ISSN : 2187-1108
Print ISSN : 2187-1094
ISSN-L : 2187-1094
Letter
Harmonics Compensation in Three-Phase Four-Wire Distribution Feeders With a Four-Leg Structured Active Power-Line Conditioner
Yuya KiharaSeita HikosakaHiroaki YamadaToshihiko TanakaFuka IkedaMasayuki OkamotoSeong Ryong Lee
Author information
JOURNAL FREE ACCESS

2020 Volume 9 Issue 5 Pages 605-606

Details
Abstract

This article deals with harmonics compensation with a four-leg structured active power-line conditioner (APLC) in three-phase four-wire distribution feeders (TPFWDFs). The instantaneous power flowing into the APLC shows that the constant DC-capacitor voltage-control (CDCVC) of the four-leg structured APLC obtains balanced and sinusoidal source currents with a unity power factor (PF) at the point of common coupling (PCC). A reduced-scale experimental model is constructed and tested. Experimental results demonstrate that balanced and sinusoidal source currents with a unity PF at the PCC are achieved with the CDCVC-based method of the four-leg structured APLC, compensating harmonic, unbalanced-active, and reactive currents in TPFWDFs.

Content from these authors
© 2020 The Institute of Electrical Engineers of Japan
Previous article Next article
feedback
Top