IEEJ Journal of Industry Applications
Online ISSN : 2187-1108
Print ISSN : 2187-1094
ISSN-L : 2187-1094

This article has now been updated. Please use the final version.

A Study of Fault Diagnosis Method using Load Currents of Linear Motor Driven Circuit Breakers
Yu HasegawaYasuaki AoyamaDaisuke Ebisawa
Author information
JOURNAL FREE ACCESS Advance online publication

Article ID: 23001556

Details
Abstract

In this paper, abnormal modes during operation are organized to evaluate the reliability of circuit breakers driven by linear motors. Next, an algorithm that automatically estimates the acceleration time from the load current of the linear motor and detects abnormalities in the circuit breaker from the acceleration time is examined. We report on the results of detecting abnormalities in mechanical components in an operation test of the circuit breaker with the proposed algorithm applied.

Content from these authors
© 2023 The Institute of Electrical Engineers of Japan
feedback