IEEJ Journal of Industry Applications
Online ISSN : 2187-1108
Print ISSN : 2187-1094
ISSN-L : 2187-1094

This article has now been updated. Please use the final version.

Experimental Confirmation of Constant DC-Capacitor Voltage-Control-Based Strategy for an Active Power-Line Conditioner
Yuka SabiHiroaki YamadaToshihiko TanakaFuka IkedaMasayuki OkamotoSeong Ryong Lee
Author information
JOURNAL FREE ACCESS Advance online publication

Article ID: L22000523

Details
Abstract

This article presents an experimental confirmation of a constant DC-capacitor voltage-control (CDCVC)-based strategy for an active power-line conditioner (APLC) in three-phase four-wire distribution feeders (TPFWDFs). A calculation block of the fundamental-active current in the feeder currents is added to the previously proposed CDCVC-based strategy for the APLC in a laboratory-scale experimental model. The experimental results demonstrate that the DC component of the output value of a proportional-integral (PI) controller in the CDCVC block is reduced by the injected fundamental-active current in the feeder currents, which is calculated by the added fundamental-active current calculation block. The PI controller in the CDCVC block of the APLC calculates the fundamental-active current in the feeder currents.

Content from these authors
© 2022 The Institute of Electrical Engineers of Japan
feedback
Top