電気学会論文誌B(電力・エネルギー部門誌)
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
論文
発電機の無効電力出力制約を考慮した電力系統の電圧安定限界
片岡 良彦篠田 幸男
著者情報
ジャーナル フリー

2003 年 123 巻 6 号 p. 704-717

詳細
抄録

This paper investigates transfer limit surface as a key to voltage stability of electric power system. Transfer limit surface is defined in nodal loading parameter space as a set of critical points. It is concluded that transfer limit surface of general power system with inequality constraints is considered to be continuous, non-smooth, and convex under some realistic assumptions. It should be noted that the non-smoothness is not so serious. Above properties of transfer limit surface is confirmed numerically through examples of two small-scale power systems with inequality constraint(s). Numerical methods to compute normal vector of transfer limit surface in the context of continuation methods are also shown.

著者関連情報
© 電気学会 2003
前の記事 次の記事
feedback