2005 年 125 巻 12 号 p. 1177-1186
It is very effective to enhance the robustness of control over the faults occurred in power system in order to realize stable and reliable power supply. The sliding mode control based on the Variable Structure System (VSS) theory is paid attentions as one of the promising robust control scheme. In the sliding mode control, the structure of the control system is changed across the hyper plane (switching plane) in state space so that the state variables of the system are kept on the hyper plane.
This paper proposes a novel control method of generator's excitation system in which the concept of sliding mode control is employed. More specifically, the proposed method switches the reference voltage used in AVR according to the sign of switching function. This paper also discusses the systematic design procedure of the optimal hyper plane. Performance and effectiveness of the proposed control method are investigated through both numerical studies and experimental tests using the single-machine infinite-bus system simulator. Both results show that the proposed control method can damp the transient swing caused by a fault effectively.
J-STAGEがリニューアルされました!https://www.jstage.jst.go.jp/browse/-char/ja/