電気学会論文誌B(電力・エネルギー部門誌)
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
論文
侵入雷サージの家屋内線における電圧電流分布の検討
饗場 潔岡部 成光宮崎 輝
著者情報
ジャーナル フリー

2007 年 127 巻 11 号 p. 1168-1176

詳細
抄録
Damage of home appliances, such as personal computers and fax machines has a great influence on highly sophisticated information society. Surge protective devices (SPD) are expected to be prevalent because installation of the SPD at a switchboard is recommended in the regulation on indoor wires revised in 2005.
In this study, experiments were conducted with a full-scale distribution system and interior wiring in order to clarify lightning response to surges intruding from service wires. The results confirmed that SPD at a switchboard with common grounding wire is effective for protecting home appliances. But in some cases, surge current could propagate into communication lines when the ground wires of SPDs at a switchboard and of a communication appliance are connected each other.
著者関連情報
© 電気学会 2007
前の記事 次の記事
feedback
Top