同期発電機を有する需要家の配電系統故障時における連系継続可能時間に対する限流器導入効果
飯岡 大輔西田 忠光横水 康伸松村 年郎
著者情報
ジャーナル フリー

2008 年 128 巻 7 号 p. 929-936

詳細
抄録
Distributed generators will be disconnected from a grid with a short-circuit fault to protect the generator and load in the customer system. In order to keep an isolated operation of the generator after the disconnection of customer system from the utility system, the customer system must adjust the power balance between supply and demand. This paper has investigated an influence of a fault current limiter on a probability of isolated operation after the disconnection of customer system with a synchronous generator from a medium voltage feeder. An allowable interconnecting time period, which is a critical time period from the fault occurrence to the isolated operation, has been simulated. It was assumed that the fault current limiter was installed in an interconnecting line between customer system with the synchronous generator and power distribution system. It was found that a resistive type fault current limiter does not improve the allowable interconnecting time period since the consumption power of fault current limiter causes the generator to decelerate. However, it was shown that the allowable interconnecting time period increases owing to the application of inductive type fault current limiter. This is because the active power of load is nearly equal to the generator output.