Much of oil filled (OF) cable has been used for a long time for 66∼500kV extra high voltage cable. Sometimes we can see extremely degraded tanδ oil (several tens % of tanδ, for example) in joint box etc. The calculation results of tanδ on a simple combination model of paper/oil show that, tanδ of oil impregnated paper with such a high tanδ oil is extremely high and it must result in a thermal breakdown. However such an event has not taken place up to the present in actually operated transmission line. This fact suggests that some suppression mechanism of tanδ has acted in the degraded tanδ oil impregnated paper insulation.
Therefore we investigated the tanδ characteristics of oil impregnated paper with extremely high tanδ oil in detail. In addition, based on the investigation results, we developed a simulation method of heat generation by dielectric loss in OF cable joint (which has degraded tanδ oil).