2009 年 129 巻 7 号 p. 935-940
This paper shows the simulation of SLF interrupting performances for SF6 gas circuit breakers. From the measurements using 300kV-SF6 gas model circuit breakers, it was shown that the extinction peak voltages were varying with arcing times. But, the current values at the extinction peak were the same.
To simulate the SLF interrupting performances for the circuit breakers, serially connected 3 arc models were used. Cassie arc model and two Mayr arc models were serially connected. In this arc model, the Cassie model simulates the high current arc. One of the Mayr arc model (Mayr model 1) simulates the arc around the voltage extinction peak. And the other Mayr arc model simulates the arc around current zero. In this model, arc voltage of the Cassie model and arc power loss of the Mayr model 1 are only estimated from the experiments. It was good agreement with the measurements and simulations.
J-STAGEがリニューアルされました!https://www.jstage.jst.go.jp/browse/-char/ja/