無効電力補償装置用交流フィルタの新設計手法と実系統試験結果との比較検討
田村 裕治高崎 真司色川 彰一武田 秀雄高木 喜久雄野呂 康宏雨谷 昭弘
著者情報
ジャーナル フリー

2011 年 131 巻 11 号 p. 876-884

詳細
抄録
AC filter design method for SVC and HVDC is commonly known in the relevant CIGRE technical brochure and IEC technical report. However the conventional method requires many iterative calculations of the harmonic voltages and currents until the calculation results become within the regulation levels by changing filter parameters based on the experience. In this respect, a new improved design method is proposed, which enables efficient evaluation on the complex impedance plane to confirm as to whether the proposed filter impedance is in the permissible range. In an actual project of Okuura SVC of Kyusyu Electric Power Co., Inc., the new method was applied to the AC filter design. This paper describes on the actual procedure of the AC filter design with the new method, the actual references of the harmonic performance calculation, and the field test measurement results on Okuura SVC. The calculation results and the filed measurement results are consistent with each other, thus the validity of the new design method is verified on its accuracy and effectiveness.