In this paper, the authors propose an improved identification method of the magnetizing inrush current phenomena. A first improvement is the development of determinant method about the transformer connection, which gives a calculation method of magnetic flux, using with theoretical pattern of inrush current ratio. And then, since the Aitken's Δ2-process, which uses the estimation of the saturation on/off time, has many extrema, it is difficult to determinate the saturation on/off time. Therefore, using the pattern of derivative current, a new determinant method of the saturation on/off time is developed.