2013 Volume 133 Issue 3 Pages 237-247
This paper presents a novel system reduction method which enables to consider the impact of PV penetration on the transient stability precisely. The object system for system reduction can be aggregated into the simple equivalent circuit by using the proposed method. The equivalent circuit consists of a lumped load model, a lumped PV model, and three equivalent impedances. Using the equivalent circuit, power flow into the object system when system voltage changes can be analyzed without repeated power flow calculation of the original system. In order to verify the proposed method, this paper presents the numerical example of transient stability analysis with one-generator-to-infinite-bus system model. The results of analysis indicate that the transient stability considering PV penetration can be analyzed with high accuracy with the proposed method.