抄録
Deterioration diagnosis of a lead acid battery by phase change between impedance and reactance was measured. The measurement frequency of inner impedance was changed from 100Hz to 5kHz. The lead acid battery with 11V open terminal voltage at the charge condition of 60% was judged as enabled in case the phase of impedance was more than 35 degrees when the application limit is CCA 180 Ampere.