極度tanδ悪化接続部を含むOFケーブル線路の劣化特性
中出 雅彦永田 健一加藤 栄士舘野 祐二
著者情報
ジャーナル フリー

2015 年 135 巻 10 号 p. 638-643

詳細
抄録
Much of oil filled (OF) cable has been used for a long time for 66 to 500kV extra high voltage cable. Sometimes we can see extremely degraded oil (several tens % of tanδ, for example) in joint box etc, but even with that sever situation, an event such as thermal breakdown has not taken place up to the present in actually operated transmission lines.  The authors have reported the tanδ characteristics of oil impregnated paper with extremely high tanδ oil and the development of a simulation method of heat generation by dielectric loss in OF cable joint.  In addition to that, the degradation characteristics of actual OF cable system have been investigated. The degraded oil distribution in actual cable system seems to be balance in nearly 27 yeas. The temperature rise of joint box is quite small even with the extremely degraded oil (tanδ=204%). With the experimental results, the OF cable system tanδ distribution is estimated and the possibility of unexpected heat generation in cable which has been installed in the conduit pipe section is proposed.
著者関連情報
© 2015 電気学会
前の記事 次の記事