電界波形に基づく雷電流波形と電荷量変化の推定精度の実証
栗原 聡史中田 英宏橋本 洋助道下 幸志
著者情報
キーワード: 電界, , 帰還雷撃, 電流, 電荷量
ジャーナル フリー

2015 年 135 巻 2 号 p. 118-124

詳細
抄録
To establish effective countermeasures on power facilities against lightning damage, it is necessary to clarify the lightning characteristics such as current parameters at the area of interest. In order to collect lightning current parameters effectively, the authors have observed electric and magnetic field waveforms simultaneously at south Kyushu, where the lightning flash density in summer is high. Based on observed electric field waveforms, the lightning current parameters have been estimated by adopting the Diendorfer-Uman model (DU model) as the return stroke model. In this paper the accuracy of the estimated return-stroke current waveform is verified by comparison with directly measured return-stroke current waveform, along with the accuracy of the estimated charge transfer from the electric field waveform measured with a slow antenna.
著者関連情報
© 2015 電気学会