電気学会論文誌B(電力・エネルギー部門誌)
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
論文
真空バルブ内真空度低下時における放電検知手法の検討
安部 淳一田辺 智子矢野 知孝吉田 暁井上 直明
著者情報
ジャーナル フリー

2016 年 136 巻 2 号 p. 154-160

詳細
抄録

The Vacuum Circuit Breaker (VCB) achieves the high current interrupting capability in the pressure lower than 10-5Pa. When gas pressure increases, the breakdown voltage of a VCB decreases according to Paschen's law, and in the case of small leak, the partial discharge will occur in the VCB and the high frequency electromagnetic waves are radiated. So, we have developed the partial discharge detection system using an antenna with the region from 200MHz to 300MHz placed inside the VCB. However, if the partial discharge occurs outside the VCB, the detection system leads to misdetection as the partial discharge inside the VCB. In order to improve the performance of partial discharge detection, the outputs of antenna voltages inside and outside the VCB are investigated.

著者関連情報
© 2016 電気学会
前の記事 次の記事
feedback
Top