ビル用マルチ空調設備群のFastADRにおける電力制限量配分のための室温副作用予測モデル
奈良村 拓森川 純次蜷川 忠三
著者情報
ジャーナル フリー

2016 年 136 巻 4 号 p. 432-438

詳細
抄録
In this paper, we have constructed an Auto Regressive(AR) and Neural Network (NN) combined type prediction model for responsive change in the room temperature trend due to the Fast Automated Demand Response (FastADR) power limitation of office building air-conditioning facilities. We defined the average of differences between room temperature and setpoint of each indoor unit for the entire building as a FastADR side-effect index for the building. Prediction experiments using an actual office building showed that the root mean square prediction error of our model was 0.23 degrees Celsius for 5 minutes after the FastADR. This prediction ability is considered sufficient to estimate the side-effect of FastADR power limitation.