耐アーク試験時の過酷さに発弧用金属線が及ぼす影響評価
—発弧用金属線の有無によるアーク特性比較—
田中 慎一神足 将司田所 兼合田 豊
著者情報
ジャーナル フリー

2017 年 137 巻 6 号 p. 476-483

詳細
抄録

Metal wires are widely used for arc ignitions in power arc tests on electrical power installations, and their material and thickness are selected variously. However, the material and thickness of the metal wire are thought to be influential factors in the severity of the power arc test, because they may change the arc duration and the physical characteristics of arc. In this paper, we made the experiment, where arcs were generated in a closed chamber by two ignition methods. one was with using various metal wires for ignition, and another was without using them, namely with causing dielectric breakdown due to imposing the impulse high voltage. From the results, the difference of characteristics between arcs with and without using metal wires for ignition was investigated, focusing on the arc energy and the internal pressure rise, which can be seen as indexes of the severity of the power arc tests. Consequently, we pointed out that the severity of the power arc tests with using metal wires investigated in this study may be equal to or more than that of the tests with causing dielectric breakdown if there is little difference in the time integral of current during the arcing time.