ITER NBI用-1MV直流フィルタと高電圧直流計測器の開発
高橋 暁史田中 敏明藤田 裕幸平沼 祐輝市村 智渡邊 和弘柏木 美恵子前島 哲也
著者情報
キーワード: フィルタ, DC, SF6ガス, 分圧器, CT, ITER
ジャーナル フリー

2018 年 138 巻 2 号 p. 166-174

詳細
抄録

This paper presents the development results of a -1MV DC filter and DC measurement systems for an ITER neutral beam injector system. High accuracy of 0.5% and fast responsivity of 3.3µs, -3dB are required for the DC measurement systems: both DC voltage dividers and DCCTs. Circuit design and thermal flow design were carried out to clarify and minimize their effects on the accuracy and responsivity. The validity of the established design was demonstrated by the actual-product tests; temperature rise of each components fell below the allowable value; inner components of DC filter withstood DC -1.2MV; each voltage divider accurately measured the voltage during the DC -1.2MV withstand voltage test; the voltage dividers and the DCCTs were adequate to the requirements of responsivity (3.3µs, -3dB).