再生可能エネルギーのFRT機能とDVS機能の価値比較
定塚 剛入口 毅駒見 慎太郎
著者情報
ジャーナル フリー

2018 年 138 巻 6 号 p. 466-472

詳細
抄録

Although FRT capability is claimed in Japanese grid code for RE, DVS capability is not. In some European countries, not only FRT but also DVS is claimed. Whether this choice of our grid code is pragmatically adequate or not? To answer the question, it is necessary to evaluate FRT and DVS capabilities. But the past studies only evaluated qualitative merit of FRT and DVS, or evaluated quantitative merit on fictional system models. Since the authors intend to evaluate FRT and DVS capabilities in existing power system of Japan, some method for the evaluation must be invented.

For the evaluation, values of FRT and DVS capabilities are evaluated by reduction amount of stabilizing equipment (i.e. SVC in the paper). The evaluation based on strict optimal SVC disposition is quite difficult, because existing power system must be adequately modeled, because number of SVCs is large and because every power flow conditions must be considered. However, semi-optimal SVC disposition can be calculated as shown in the paper.

As the result, value of FRT is quite larger than value of DVS. And then, our grid code is proved as pragmatically adequate, except some flaw in claimed FRT design that is introduced in the paper.