特集論文
ステップ注入付周波数フィードバック方式に起因するフリッカ発生要因の実験的検証
白崎 圭亮岡田 有功佐野 憲一朗岩月 秀樹
著者情報
ジャーナル フリー

2018 年 138 巻 8 号 p. 651-658

詳細
抄録

Flicker may be caused by “frequency feedback method with step injection of reactive power” installed in PCS which is generally used as grid-connected inverter in Japan. Therefore, in this paper, characteristics of the flicker were investigated by experiments with actual PCS in single phase circuit. Furthermore, effective means for suppressing the flicker was considered by taking the cause of occurrence of flicker into account. Moreover, it was clarified the differences among PCSs on flicker using multiple actual PCSs. In conclusion, gain of frequency feedback function should be reduced as one of effective means to avoid flicker.