IEEJ Transactions on Power and Energy
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
Special Issue Paper
Criterion for Continuous Oscillation of Reactive Power caused by the Frequency Feedback Method with Step Injection of Reactive Power
Kenichiro SanoNaotaka OkadaKeisuke ShirasakiHideki Iwatsuki
Author information
JOURNAL FREE ACCESS

2018 Volume 138 Issue 8 Pages 659-670

Details
Abstract

This paper focuses on the continuous oscillation of reactive power caused by the frequency feedback method in the grid-connected inverters. The transfer functions of inverter and ac system are derived. Then the stability of the system is analyzed according to the transfer functions. The analysis clarified that the system becomes unstable if the product of line impedance, inverter capacity, and frequency feedback characteristic exceeds a specific threshold value. Then it results in the continuous oscillation of reactive power.

Content from these authors
© 2018 by the Institute of Electrical Engineers of Japan
Previous article Next article
feedback
Top