電気学会論文誌B(電力・エネルギー部門誌)
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
特集論文
高圧配電線の構成が直撃雷による相間スパークオーバ発生率に与える影響
山口 宜大石本 和之森 亮太河野 丈治
著者情報
ジャーナル 認証あり

2022 年 142 巻 2 号 p. 114-120

詳細
抄録

In recent years, to reduce maintenance and management cost of distribution facilities, overhead ground wires are sometimes removed in a certain area. In such distribution lines, wire breaking at mid-span due to direct lightning is of concern. Although phase to phase sparkover is considered to be one of the factors of wire breaking at mid-span, its quantitative study has not yet been carried out. In this paper, at first, we experimentally examined detailed sparkover characteristics between phase conductors against short tail lightning impulse voltage, which is assumed to be phase to phase voltage. Next, based on experimental results, we estimate the phase to phase sparkover rate by means of lightning outage calculation program developed by CRIEPI. Estimated results suggest the phase to phase sparkover rate depends on the configuration of distribution lines, such as span length, arrangement of conductors, and so forth.