風力発電システムにおける雷による電力ケーブル着火に関する実験的検討
関 健一土田 崇秋葉 睦多田 博幸関岡 昇三
著者情報
ジャーナル 認証あり

2024 年 144 巻 1 号 p. 23-29

詳細
抄録

A separable connector is used for the power cables and apparatuses in renewable energy systems. The shield of the collector cable is sometimes an open circuit at one end to reduce power loss due to the shield current. However, this has a disadvantage from the viewpoint of lightning protection. The semi-conductive part of the separable connector is grounded for safety. The ground potential rise due to a direct lightning strike to a wind tower sometimes damages the collector cables and power apparatuses in the wind tower. Combustion in a cable is one of the most serious types of lightning-caused damage. This paper describes an experimental study on fire ignition in a collector cable caused by a ground potential rise due to a direct lightning strike to a receptor. The mechanism leading to fire ignition is discussed based on the experimental results. This paper also proposes a countermeasure against such fire ignition.

著者関連情報
© 2024 電気学会
前の記事 次の記事