超電導発電機と従来形発電機の並行運転時の三相短絡故障による過渡安定限界に関する考察
仁田 旦三白井 康之小川 喜弘河内 俊和岡田 隆夫
著者情報
ジャーナル フリー

1994 年 114 巻 11 号 p. 1135-1141

詳細
抄録
In order to understand some characteristics on superconducting generators (SCG's) in power systems, experimental studies by using the 20kVA SCG have been performed. It is necessary to inverstigate the characteristics for parallel operations of an SCG and a conventional generator(CG) when an SCG is installed to a present power station. In this paper, we describe some results of our studies on parallel running of the 20kVA SCG and the 20kVA CG. In the experimental system, the SCG is connected to regional power system (infinit bus) through reactors (artifical transmission lines) and the CG is connected to the terminal of the SCG. By the experiments and computer simulation, we investigate the transient characteristics at three-phase short-circuit faults 1) when CG is not isolated and 2) when CG is isolated after reclosing. We obtain two kinds of stable limit curves for output power at three-phase short-circuit fault for above two cases.