直流重畳法の水トリー劣化検出感度およびその適用限界の検討
新元 孝木村 千秋山本 憲梅田 進
著者情報
ジャーナル フリー

1995 年 115 巻 10 号 p. 1148-1153

詳細
抄録
In recent years, as one of the methods that permit effective and efficient maintenance of medium voltage XLPE insulated cables (CV cables), the DC superimposition method which is used to measure insulation resistance under hot-line condition has attracted attention, and efforts are being made to promote its practical application. However, there still remain some problems to be solved in applying this method.
The authors, therefore, considered the detection sensitivity of the DC superimposition method applied to a water-tree deteriorated CV cable, and examined the application limit of this method on system voltages. As a result, the following points were clarified: (1) this method can detect penetrated water-trees, (2) the upper limit of the residual insulation breakdown strength of a deteriorated cable should be considered 10kV, and (3) this method can be applied to system voltages below 6.6kV.