落雷位置標定システムの精度と落雷頻度マップの送電線トリップ事故に基づく評価
新庄 一雄若井 武夫酒井 勉石井 勝
著者情報
ジャーナル フリー

1997 年 117 巻 11 号 p. 1448-1457

詳細
抄録
Accuracy of an LLP system and a lightning frequency map is evaluated by using transmission line faults in Hokuriku area from November in 1993 to October in 1996. The accuracy and efficiency of the system were calculated by statistical methods. From the above results, the lightning frequency map with 10 minutes meshes was proved capable of replacing the Isokeraunic Level Map with 15 minutes meshes used now for lightning protection design. However, the correlation between the number of detected lightning flashes and transmission line faults in each mesh was found to be week. This result suggests that more detailed analysis taking account of the length of transmission lines in each mesh is necessary. The correlation is stronger in winter than in summer, despite the fact that there is difference in the lightning current distribution in each mesh in winter. This characteristic can be explained if upward flashes from transmission lines are dominant among lightning faults in winter.