電気学会論文誌B(電力・エネルギー部門誌)
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
自然雷および誘雷に対する送電線の過渡応答特性
新庄 一雄松本 安弘佐久 間治若井 武夫酒井 勉石井 勝本山 英器
著者情報
ジャーナル フリー

1997 年 117 巻 4 号 p. 478-487

詳細
抄録
Measurement of lightning surges originating from natural and rocket-triggered lightning strokes in winter has been carried out on a real-size test transmission line since 1987. During November 1993 to December 1995, fifteen flashes which struck the test transmission line were observed. In one of the fifteen cases, the arresters equipped on the test transmission tower operated and well controlled the voltages across the insulators. In another case, a four-phase backflashover was observed on the upper and middle phases. The calculated results of the multi-phase analysis by EMTP agreed with the measured waveforms when the timing of the flashovers was given. But the four-phase flashover phenomenon was explained neither by the integration method nor by the leader development model.
著者関連情報
© 電気学会
前の記事 次の記事
feedback
Top