電気学会論文誌B(電力・エネルギー部門誌)
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
多重カスケード接続変圧器の電位分布特性
中島 達人鈴木 宏和松尾 尚英斉藤 達稲垣 恵造
著者情報
ジャーナル フリー

1997 年 117 巻 5 号 p. 641-646

詳細
抄録
Voltage distribution for lightning surge in multi-cascaded transformer, that will be used for a converter transformer in self-excited DC transmission, was studied using model transformers. There was good agreement between measured data and calculated results. It was cleared that our calculation program have enough performance for estimating voltage distribution.
Maximum voltages in high-voltage windings for lightning surge were below 120% and transfer voltages to converting circuit were below about 5%. Therefore, there were no serious problems in cascaded transformers for lightning surge. However, their voltage distribution was not satisfactory when same transformers were connected in cascade. We clarified with simulation that the distribution could be improved by modifying every transformer's structure according to position in cascade connection.
著者関連情報
© 電気学会
前の記事 次の記事
feedback