洞道内に布設した長距離GILの部分放電伝搬特性と測定技術
佐々木 賢次宮崎 明延五味 善昭滝波 直樹荒木 智勇二島 英明須藤 彰久山口 泰朗亀井 光仁宮下 信
著者情報
ジャーナル フリー

1997 年 117 巻 8 号 p. 1181-1188

詳細
抄録

This paper deals with the results of various partial discharge detection tests designed to clarify fundamental characteristics, which were carried out on a real-scale 275kV GIL test line laid through a tunnel, along with a solid partial discharge testing technique for a long-distance GIL.
Where it is required to secure dependable reliability for a long-distance and large-capacity gas-insulated transmission line ( GIL), strict quality control and electrical tests carry serious weight with verifying its integrity, during the construction work.
Among others, “Partial Discharge Detection” is extremely instrumental in examining GIL insulation for defects or damage. But its performance has not yet been fully brought to light, namely, sensitivity to faint signals from incidental partial-discharge. how the detection is influenced by assorted modes of external noise. and whether or not to catch how faint partial discharge signals act in a long-distance transmission line . In particular no dependable partial discharge testing technology was available for long gas-insulated transmission lines.