電気学会論文誌B(電力・エネルギー部門誌)
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
Second-kick改善法を適用したエネルギーベース指標によるSVCの安定度向上効果の検証
橋本 博幸田岡 久雄Madeline GibescuCheng-Ching Liu
著者情報
ジャーナル フリー

2002 年 122 巻 1 号 p. 103-112

詳細
抄録
The main purpose is to evaluate the effectiveness of SVC installation from the viewpoint of an energy-based index. Although transient and voltage stability - due to distinct mechanisms and separate time frames - have been perceived as decoupled phenomena by some researchers, in this work they are treated as aspects of coupled power system dynamics. The time-domain simulation uses detailed models for system components and controllers including SVC. Based on the trajectories obtained, an energy value can be calculated for every point in time. The energy function formulation is developed using injection models. The measure of stability used is the energy margin. This is computed based on the well-known second-kick method. A new second-kick design better suited for exploring voltage instability mechanisms is proposed, which consists of a combination of load step and fault. The better timing of applying a second-kick disturbance is also studied. Results are shown for a standard IEEJ test system. Energy margins and unstable equilibrium point approximations are calculated for the conventional and new second-kick designs. It is seen that the energy margin is dependent on the nature of the disturbance. SVC's are expected to improve stability by providing fast reactive power support at key load buses. Improved energy margins are observed when these devices are available.
著者関連情報
© 電気学会
前の記事 次の記事
feedback
Top