電気学会論文誌B(電力・エネルギー部門誌)
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
変電所がいしの汚損度測定時期と洗浄時期の自動決定
中村 政俊黄 偉後藤 聡谷口 孝
著者情報
ジャーナル フリー

2002 年 122 巻 2 号 p. 314-322

詳細
抄録
Insulators in coastal substations are polluted due to the salty wind blowing from the sea. The insulator pollution may cause higher leakage current and ultimately give rise to blackouts due to flash-over. To avoid those accidents, the insulators are frequently washed using much amount of pure water. Almost all measuring devices use a pilot insulator, which is exposed to the same conditions as the actual insulators, and measure the pollution deposits on the pilot insulator at each measurement interval. However, when measuring the pilot insulator (15 minutes), the pilot insulator is not being exposed. Therefore the larger the times of measuring, the more errors will be resulted. This research aims at developing a method of reliable decision making of timing for measuring and washing of the polluted insulators. The proposed method is derived based on the prediction of pollution deposits by use of the insulator pollution model. Effectiveness of the proposed method was demonstrated by applying it to actual data taken from Karatsu substation in Japan.
著者関連情報
© 電気学会
前の記事 次の記事
feedback
Top