22kV配電系統の中性点接地方式検討
商用周波モデルによる地絡事故時の電圧・電流分布の解析
岡 圭介吉永 淳小泉 覚上村 敏有賀 保夫
著者情報
ジャーナル フリー

2002 年 122 巻 3 号 p. 401-407

詳細
抄録
To cope with restructuring of electricity market, application of 22kV distribution system to areas with high load density, is promising. In this paper, we have studied the neutral grounding method considering low voltage rise and induced voltage to communication line in case of ground fault. We have performed EMTP(Electro-Magnetic Transients Program) simulation on several distribution system models with variation of line length and assembling representing actual distribution systems. We have also compared the simulation result with measurement performed on line imitating actual 22kV distribution line to confirm the accuracy of simulation result. Consequently, we have clarified the permissible range of neutral grounding resistance.