電気設備学会誌
Online ISSN : 2188-6946
Print ISSN : 0910-0350
ISSN-L : 0910-0350
論文
建築構造体接地抵抗の計算手法に関する考察
森田 祐志高橋 健彦
著者情報
ジャーナル フリー

2012 年 32 巻 2 号 p. 161-167

詳細
抄録
Reinforced concrete used for the basement of building generally has a certain electrical conductivity and a large contact area with the soil. Hence it can be used for earthing purpose. ln order to use the building basement as earthing electrode,it is necessary to confirm that the earthing is below resistance 2Ω prescribed in Ministerial Ordinance of Technical Standards for Electrical Facilities Interpretation article 22. To estimate the earthing resistance by calculation,the building basement is generally replaced by ah hemisphere electrode having the same surface as the basement. In this paper,earthing resistance obtained by three kinds of calculation methods are compared and discussed.
著者関連情報
© 2012 一般社団法人 電気設備学会