Energy Saving Potentials of a 100% Outdoor Air System Integrated with Indirect and Direct Evaporative Coolers for Clean Rooms
Kim Min-HwiKwon Oh-HyunJin Jeong-TakChoi An-SeopJeong Jae-Weon
著者情報
ジャーナル フリー

2012 年 11 巻 2 号 p. 399-405

詳細
抄録
In general, HVAC systems for clean room facilities require significant energy to maintain the indoor environment. Due to high air change rates, reducing operating energy consumptions has been a critical issue. The purpose of this paper is to investigate the energy saving potentials of indirect and direct evaporative cooler assisted 100% outdoor air system (IDECOAS) serving a clean room. This research also provides a practical insight on how cooling and heating coil loads can be reduced and how to design the proposed system. In this study, it was assumed that a clean room is served by four different types of HVAC systems: a variable air volume system (VAV), an air washer system (AIRWASH), a dedicated outdoor air system (DOAS), and IDECOAS. It was found that DOAS and IDECOAS can reduce the annual cooling and heating coil loads by over 65.7% and 59.5%, respectively, compared with the VAV.