Journal of Asian Architecture and Building Engineering
Online ISSN : 1347-2852
Print ISSN : 1346-7581
Environmental Engineering
Evaluation of the Introduction of a Combined Heat and Power System in a Commercial Building in Shanghai
Ji XuanWeijun GaoYingjun RuanXindong WeiRyan Firestone
著者情報
ジャーナル フリー

2006 年 5 巻 2 号 p. 385-390

詳細
抄録
This paper discusses the evaluation of a proposed combined heat and power (CHP) system for Jin Mao Tower (JM Tower), a commercial building in the centre of Shanghai. Because of the essential similarity in climate condition and latitude between Shanghai and Tokyo, electricity and heating consumption estimates are based on available Tokyo data. However this study does point out degree-days in order to guarantee the accuracy of energy consumption intensities of Shanghai. Two types of energy supply systems are considered: conventional and CHP. Environmental impact and economic efficiency are evaluated regarding the efficiency of both systems. Relative to the conventional system, CHP is capable of reducing the primary energy consumption by 23% and CO2 emission by 36%. The total annual running cost savings - the sum of energy, maintenance, and labour costs - are 11.8 million RMB, with a payback period of 3.8 years.
著者関連情報

この記事は最新の被引用情報を取得できません。

© 2006 Architectural Institute of Japan
前の記事 次の記事
feedback
Top