Study on the Installed Filter Leakage Evaluation Criterion for Particle Counter and Aerosol Photometer
Muhammad Aiman MOHD NORYoshihide SUWA
著者情報
ジャーナル フリー

2020 年 35 巻 1 号 p. 34-42

詳細
抄録

 In order to examine the criterion of leak testing of installed filter systems shown in ISO 14644-3: 2005, evaluations of particle concentration at downstream of installed filter systems by particle counters and aerosol photometers were compared, assuming the same upstream concentration distribution. As the result of numerical calculations, although particle counters and photometers detected different penetration rate values, a reasonably good correlation was observed between both instruments within the allowable requirements for the upstream particle concentration distribution stated in ISO 14644-3. A possibility to use the same evaluation criterion for both instruments was also studied. Based on the results obtained, it was found that the same standard leakage evaluation criterion could be applied to the filters with a performance of H14 (BS-EN 1822-1: 2009) or higher. However, for the filters with a performance of H13 and lower, it was considered unreliable to apply the same criterion. Currently, the ISO 14644-3: 2005 is too complicated, different criterion for particle counters and photometers are presented. Moreover, the criterion changes for particle counter at different filter grades used in the tested rooms. The findings obtained in this study will simplify the complexity exists in the current ISO standard.

著者関連情報
© 2020 日本エアロゾル学会