抄録
We report the experiment results on discharge in palm oil under sinusoidal voltages in small chamber. PD was measured using RC detector. The PD data was presented in the form of ф-q-n pattern and time sequential pulse train. Dissolved gas analysis due to PD in oil was also performed. The results were compared with ones in mineral oil which have been using as insulating materials in high voltage apparatus.