燃料貯蔵タンク底板外面の腐食深さ測定と超音波検査結果の検討
荒岡 礼須藤 皓水流 徹
著者情報
ジャーナル フリー

1998 年 47 巻 2 号 p. 131-135

詳細
抄録
A corrosion inspection for bottom plate of fuel storage tanks using ultrasonic thickness gauge (UT) must be performed regularly as provided by law. In order to investigate reliability of UT, corrosion depth of samples cut from bottom plates measured by laser displacement meter (LDM) was compared with results of UT. As a result, it was indicated that UT was enough to know mean corrosion depth, however maximum corrosion depth estimated statistically from corrosion depth measured by LDM was 1-1.5times larger than that from UT. It became clear that the estimated maximum corrosion depth would be smaller than the actual value when UT is used in its estimation.