液体窒素冷却500kVA級酸化物超電導変圧器の開発
船木 和夫岩熊 成卓柁川 一弘竹尾 正勝末廣 純也原 雅則山藤 馨今野 雅行笠川 勇介大久保 堅司保川 幸雄能瀬 眞一上山 宗譜林 和彦佐藤 謙一
著者情報
ジャーナル フリー

1998 年 33 巻 6 号 p. 371-381

詳細
抄録

We have designed and constructed a 500kVA-class oxide-superconducting power transformer. The windings are cooled by liquid nitrogen or subcooled nitrogen in a G-FRP cryostat of 785mm in diameter and 1, 210mm in height, that has a room-temperature space for an iron core with the diameter of 314mm. The primary and secondary windings are three-strand and six-strand parallel conductors of a Bi-2223 multifilamentary tape with silver sheath, respectively. The strand of 0.22mm thick and 3.5mm wide has 61 filaments with no twisting. The ratio of superconductor is 0.284. In the parallel conductors, the strands are transposed five times in each layer for a uniform current distribution among them. It was proved that the transformer has the rated capacity of 500kVA by means of two-hours short-circuit test and half-hour no-load test in liquid nitrogen of 77K. The efficiency is estimated as 99.1% from a core loss of 2.3kW and a thermal load of 2.2kW in coolant. The latter is composed of AC losses in windings and heat leakage from the cryostat and current leads, and is multiplied by a refrigeration penalty of liquid nitrogen, 20. Load test was also performed up to 500kVA. The transformer was furthermore operated in subcooled nitrogen at 66K with no quenching up to a critical level, that is equivalent to 800kVA. The efficiency estimated was improved to 99.3% in subcooled nitrogen. Measured AC loss in both windings are well explained by a theoretical prediction with the ‘critical state model.’ We also discuss prospective applications of the parallel conductors composed of advanced HTS multifilamentary tapes to AC windings with large current capacity.

著者関連情報
© 社団法人低温工学協会
前の記事 次の記事
feedback
Top