照明学会雑誌
Online ISSN : 2185-1506
Print ISSN : 0019-2341
ISSN-L : 0019-2341
平均照度法による室内照明計算
飯塚 昌之重見 健一石野 幸三
著者情報
ジャーナル フリー

1968 年 52 巻 8 号 p. 478-485

詳細
抄録

Average illumination is one of the most important indices in illuminating engineering. The lighting design often includes a prediction of the average illumination on the working plane or on the floor and the illumination and luminance distributions within the room. But, to calculate the value of it theoretically is quite difficult becase of the complexity of the calculatin. conditions. In that case, measuring is only way to obtain the values.
For the calculations of average illumination, the authors used average illumination method in which readings taken at specified positions are weighted according to their positions.
In this paper, to estimate the errors of the average illumination method and know its practicality and usefulness the following process was taken.
1. Obtain average illumination by interreflection method and regard it as standard illumination.
2. Obtain illumination distributions at specified positions-by-point by point method and using them get approximate value of average illumination.
3. Compare average illumination by interreflection method with the above values for various room conditions.
In case of luminous ceiling and panel lighting, the authors confirmed the practicality of average illumination method under various conditions.

著者関連情報
© (社)照明学会
前の記事 次の記事
feedback
Top