110 差圧伝送器による導圧管の詰まり診断に関する研究 : 第1報:揺動のRMS値による診断
栄野 隼一涌井 徹也橋詰 匠宮地 宣夫齋藤 洋二西島 剛志桑山 秀樹
著者情報
会議録・要旨集 フリー

詳細
抄録

Differential pressure transmitters with an orifice are widely used as field flow meters. The typical trouble of the differential pressure transmitters under operation is an impulse line blockage. Thus, the authors develop a detecting method of the impulse line blockages using the R.M.S. value of fluctuations of measured pressures. This method always monitors not only the fluctuation of differential pressure but also those of two static pressures, which means the high side pressure and low side pressure. The experimental investigations show that this monitoring makes it possible to detect a both side blockage and either side blockage before the blockages have an serious influence on measuring the differential pressure.