環境工学総合シンポジウム講演論文集
Online ISSN : 2424-2969
セッションID: 416
会議情報
416 換気空調融合システムのエネルギ評価(エネルギー需給と空調システム評価・解析,環境保全型エネルギー技術分野)
井上 誠司斉藤 信鈴木 洋邦
著者情報
会議録・要旨集 フリー

詳細
抄録
Simulation models of three types of air conditioning system combined with ventilation have been developed. The compared systems are as follows: (A) Duct type ventilation and air conditioner, (B) Duct type ventilation and air conditioner which inhale indoor air mixed with supply air (outdoor air), (C) Total heat exchange ventilation system and air conditioner. We calculated total energy consumption and indoor humidity in order to evaluate the effects of difference of ventilating system under various combinations of outdoor air temperature and humidity. As a result, we clarified that the annual energy consumption of system (B) decreases 3.4% compared with that of system (A), because the air conditioner operates efficiently by the indoor air mixed with the supply air. And we also clarified that the annual energy consumption of system (C) decreases 9.1% compared with that of system (A), because the air conditioning load decreases by the total heat exchanger of the ventilator.
著者関連情報
© 2006 一般社団法人 日本機械学会