Proceedings of the International Conference on Power Engineering : ICOPE
Online ISSN : 2424-2942
2003.3
会議情報
B307 HEAT TRANSFER CHARACTERISTIC ON VERTICAL CIRCULAR TUBE UNDER DROPWISE CONDENSATION : Effect of the direction of cooling water on the heat transfer
Tsutomu HOSOKAWAHiroyuki SHIRAIWAToshio NAKATAFumiyoshi KIMURA
著者情報
会議録・要旨集 フリー

p. _3-111_-_3-115_

詳細
抄録
On the general heat exchanger of a vertical circular tube, cooling water is run from the bottom to the top in the tube. However, according to the last research of the dropwise condensation of authors, it is anticipated that the good heat transfer characteristic is obtained when the cooling water is run from the top to the bottom. Heat transfer characteristic on a vertical condensing circular tube was obtained by using a copper tube (o.d.40mm, i.d. 30mm and length 700mm). When the cooling water in the tube flew down and up, the heat transfer had a good characteristic in the case of water flowing down. And we evaluated the relation between the behavior of condensate drops and the heat transfer, and then, the sweeping action had a significant effect in this experimental conditions.
著者関連情報
© 2003 The Japan Society of Mechanical Engineers
前の記事 次の記事
feedback
Top