年次大会
Online ISSN : 2424-2667
ISSN-L : 2424-2667
セッションID: J0520401
会議情報
J0520401 パッケージエアコン4方向室内機における吹出し口の圧力損失低減
佐藤 大和岩瀬 拓尾原 秀司伏見 直之
著者情報
会議録・要旨集 フリー

詳細
抄録
In order to reduce the fan power of a 4-way cassette type indoor unit of a packaged air conditioner, we developed the shape of air outlet nozzles reducing of the pressure-loss. The main cause of the pressure-loss was the flow separation area shaped in current air outlet nozzles. Therefore, we devised the shape for the control of the flow separation area. The shape was defined by two parameters, and the influence of parameters on the fan power reduction was surveyed by using the simulation technology with CFD (Computational Fluid Dynamics). We used the response surface which was made by results of CFD and approximate values with the Kriging-based method since the appropriate combination of parameters was efficiently searched from multiple parameters. As the result, the combination of parameters which reduces the fan power the most in the response surface was found. The shape adopted the combination of parameters can control the flow separation area. The fan power reduction by 9.9% in comparison with the current shape of air outlet nozzles was confirmed by the experiment.
著者関連情報
© 2015 一般社団法人 日本機械学会
前の記事 次の記事
feedback
Top