動力・エネルギー技術の最前線講演論文集 : シンポジウム
Online ISSN : 2424-2950
セッションID: B211
会議情報
B211 低温排熱駆動型MH冷凍機の作動特性(OS11 廃熱利用技術)
勝田 正文〓 相哲挟田 晃司石川 敬祐春名 祐介能美 直子
著者情報
会議録・要旨集 フリー

詳細
抄録
In this study, we aim to development of heat driven type water chiller using metal hydride (briefly, MH). Heat driven type MH water chiller is one of the chemical heat pumps, and the endothermic reaction of low temperature side MH is used to the water chilling. Nowadays, because MH is expensive as 2〜30,000 yen per lkg, and the cooling load per 1kg MH is low , heat driven type MH water chiller is not used generally. For the cost-cutting of this system, we use a low price TiFe alloy, which is manufactured by co-researcher, to heat source side MH. Moreover, in order to improve the cooling load per MH mass, we mix the brush type carbon fiber. 2 mass% into MH beds. By this method, the cooling load per MH mass can be increased to 0.078 kW/kg(MH).
著者関連情報
© 2009 一般社団法人 日本機械学会