界面活性剤水溶液流れにおけるミセルブレーカの影響(オーガナイズドセッション8 伝熱促進)
荒賀 浩一高山 大輔益田 恭佑武石 正人神野 稔村田 圭治
著者情報
会議録・要旨集 フリー

詳細
抄録
In surfactant solution (TTAB+NaSal), the pipe friction factor and heat transfer coefficients were investigated. The straight circular tube of D=5.05 mm in diameter and L=2900 mm in total length was used. In the drag reduction flow, in order to break micelle structures and to promote heat transfer, the "micelle breaker (MB)" was installed in the upper stream of the testsection. The effect of MB was investigated changing surfactant solution concentration (200, 500, lOOOppm). As a result of the experiments, In the case of 1000 ppm, Re=7700, installation of the micelle breaker increased NuPr^<-1/3> at x/D=10 (x/D indicates the distance from heating section.) by 1.9 times compared with the case where it does not install. But The effect of MB mostly disappears by x/D=130. The effect of MB appears so notably that concentration is low.
著者関連情報
© 2004 一般社団法人 日本機械学会