熱工学コンファレンス講演論文集
Online ISSN : 2424-290X
セッションID: H125
会議情報
H125 ループ型サーモサイフォンの冷却性能に及ぼす作動流体の影響(OS-3:電子機器・デバイスの熱課題(2))
山下 誠也Ji-won Yeo小山 繁
著者情報
会議録・要旨集 フリー

詳細
抄録
Recently, the heat flux of electronic devices increases with rapid development of the semiconductor technology. So, a high performance cooling unit for electronic devices is required. Therefore, we have experimentally investigated the cooling performance of the loop type thermosyphon. In this paper, effects of working fluids on heat exchange performance of this loop type thermosyphon were evaluated in the heat flax ranges from 15W/cm^2 to 135W/cm^2. Two HFO refrigerants and one HFC refrigerant were tested for working fluid. The boiling thermal resistances of two refrigerants are nearly the same and less than that of the other refrigerant.
著者関連情報
© 2013 一般社団法人 日本機械学会