主催: 一般社団法人 日本機械学会
会議名: 熱工学コンファレンス2016
開催日: 2016/10/22 - 2016/10/23
Thermal load tests of the ground-coupled heat pump (GCHP) system for heating and cooling are made for evaluating the system performance and the operation characteristics. The GCHP of the experimental apparatus has direct expansion ground heat exchangers. The refrigerant in the GCHP exchanges heat directly with the ground by evaporating/condensing in the ground heat exchangers. In the heating mode, the coefficient of performance is about 3.8 and the operation behaviors are usually stable. In the cooling mode, the outputs sometimes fluctuate up and down. The phase of the refrigerant changes in the ground heat exchangers. The behavior of the refrigerant needs to be analyzed for repressing the instability in the cooling mode operations.