Development of Packaged Air Conditioners for Data Center with Outdoor Air Cooling (Analysis of Performance on Pump Cycle)
Keisuke SEKIGUCHIIMasahide YANAGI
Author information
JOURNAL FREE ACCESS

2012 Volume 78 Issue 789 Pages 1073-1077

Details
Abstract
To decrease the power consumption of air-conditioning in the data centers, a packaged air-conditioner that contained the pump cycle was developed. The new air-conditioner has improved COP when outdoor temperature is especially low. In this report, the performance at the pump cycle was evaluated with a real machine of the test site. As a result of the verification, the stability of driving at the pump cycle was confirmed. In addition, it was shown the relation between outdoor temperature and total COP, and high driving efficiency at the low outdoor temperature.